Braeburn 6100 Programmable Touchscreen Thermostat User Manual
Specifications
This thermostat is compatible with:
- Single stage heat / cool conventional and heat pump systems
- Conventional systems up to 3 stages of heating and 2 stages of cooling
- Heat pump systems up to 4 stages of heating and 2 stages of cooling
- 250 – 750 millivolt heating only systems
Electrical and control specifications:
- Electrical Rating: 24 Volt AC
- 1 amp maximum load per terminal
- AC Power: 18 – 30 Volts AC
- DC Power: 3.0 Volt DC (2 “AA” Alkaline Batteries Included)
- Control Range: 45° – 90° F (7° – 32° C)
- Temperature Accuracy: +/- 1° F (+/- .5° C)
- Outdoor Temperature Display Range: -40° – 120° F (-40° – 49° C)
Humidification Specifications
- Humidification Control Range: 10% – 50% RH
- Dehumidification Control Range: 40% – 80% RH
Terminations
Rc, Rh, G, W1/E/AUX1, W2/AUX2, W3/O/B, Y1, Y2, C, L, H, A/D, S1, S2
Installation and Wiring
Warning Disconnect power before beginning installation.
Thermostat Location
Install the thermostat approximately 5 feet (1.5m) above the floor in an area that has a good amount of air circulation and maintains an average room temperature. Avoid installation in locations where the thermostat can be affected by drafts, dead air spots, hot or cold air ducts, sunlight, appliances, concealed pipes, chimneys and outside walls.
Install your new Braeburn thermostat in 4 basic steps:
- Install the sub-base
- Provide Power
- Connect your wires
- Attach the thermostat to the sub-base
Install the Sub-Base:
- Remove the sub-base from the body of the thermostat.
- Mount the sub-base as shown below:
- Provide Power
- For 24 Volt AC power, you must connect the common side of the transformer to the C terminal on the thermostat sub-base. In dual transformer installations, the transformer common must come from the cooling transformer.
- For battery power, insert the 2 supplied “AA” type alkaline batteries into the battery compartment located in the rear housing of the thermostat. Make sure to position the Positive (+) and Negative (-) sides of the batteries correctly with the +/- symbols in the battery compartment.
Wiring Terminations
- Terminal Function Description
- H Output Humidifier
- A / D Output (A) Economizer Control, (D) Dehumidifier
- G Output Fan Control
- Rc Input 24 Volt AC Cooling Transformer
- (Dual Transformer Systems Only)
- Rh Input Power Connection (24 Volt AC Heating
- Transformer or Millivolt Power Source)
- W1 / E / Output (W1) 1st Stage Conventional Heat,
- AUX1 (E) Emergency Heat,
- (AUX1) 1st Stage Auxiliary Heat
- W2 / AUX2 Output (W2) 2nd Stage Conventional Heat,
- (AUX2) 2nd Stage Aux Heat
- W3 / O or B Output (W3) 3rd Stage Conventional Heat,
- (O) Cool Active Reversing Valve
- (B) Heat Active Reversing Valve
- Y1 Output 1st Stage Compressor
- Y2 Output 2nd Stage Compressor
- C Input 24 Volt AC Transformer Common
- L Input System Malfunction Indicator
- S1
- S2 3 Connecting Your Wires (continued) Input Optional Remote Sensor (Indoor or Outdoor)
Conventional Systems
Typical Wiring Configurations
NOTE: The “System Type” option will be configured in the Installer Settings section
Heat Only or Millivolt
- Set System Type to 11CONV
- Rh Power Connection
- W1 Heat Relay
- G Fan Relay [note 4]
- C 24 Volt AC Transformer Common [note 1]
1 HEAT / 1 COOL Single or Dual Transformer
- Set System Type to 11CONV
- Rh 24 Volt AC Power (heating transformer) [note 2]
- Rc 24 Volt AC Power (cooling transformer) [note 2]
- W1 Heat Relay
- Y1 Compressor Relay
- G Fan Relay
- C 24 Volt AC Transformer Common [note 1, 3]
2 HEAT / 2 COOL Single or Dual transformer
- Set System Type to 22CONV
- Rh 24 Volt AC Power (heating transformer) [note 2]
- Rc 24 Volt AC Power (cooling transformer) [note 2]
- W1 Heat Relay Stage 1
- W2 Heat Relay Stage 2
- Y1 Compressor Relay Stage 1
- Y2 Compressor Relay Stage 2 [note 4]
- G Fan Relay
- C 24 Volt AC Transformer Common [note 1, 3]
3 HEAT / 2 COOL Single or Dual Transformer
- Set System Type to 32CONV
- Rh 24 Volt AC Power (heating transformer) [note 2]
- Rc 24 Volt AC Power (cooling transformer) [note 2]
- W1 Heat Relay Stage 1
- W2 Heat Relay Stage 2
- W3 Heat Relay Stage 3
- Y1 Compressor Relay Stage 1
- Y2 Compressor Relay Stage 2 [note 4]
- G Fan Relay
- C 24 Volt AC Transformer Common [note 1, 3]
NOTES – Conventional Systems
- Optional 24 Volt AC common connection.
- Remove factory installed jumper for dual transformer systems.
- In dual transformer systems, transformer common must come from cooling transformer.
- If needed for system. Provide disconnect and overload protection as required.
Heat Pump Systems
Typical Wiring Configurations
NOTE: The “System Type” option will be configured in the Installer Settings section.
1 HEAT / 1 COOL – No Auxiliary Heat
- Set System Type to 11HP
- Rh 24 Volt AC Power
- Rc Connected to Rh with supplied Jumper Wire
- O/B Changeover Valve [note 2]
- Y1 Compressor Relay
- G Fan Relay
- C 24 Volt AC Transformer Common [note 1]
2 HEAT / 2 COOL – No Auxiliary Heat
- Set System Type to 32HP
- Rh 24 Volt AC Power
- Rc Connected to Rh with supplied Jumper Wire
- O/B Changeover Valve [note 2]
- Y1 Compressor 1 Relay (1st stage heating/cooling)
- Y2 Compressor 2 Relay (2nd stage heating/cooling)
- G Fan Relay
- C 24 Volt AC Transformer Common [note 1]
- L Optional System Fault Monitor [note 4]
2 HEAT / 1 COOL – Including Auxiliary Heat
- Set System Type to 22HP
- Rh 24 Volt AC Power
- Rc Connected to Rh with supplied Jumper Wire
- O/B Changeover Valve [note 2]
- Y1 Compressor Relay (1st stage heating/cooling)
- W2 Auxiliary Heat Relay (2nd stage heating) [note 3]
- E Emergency Heat Relay [note 3]
- G Fan Relay
- C 24 Volt AC Transformer Common [note 1]
- L Optional System Fault Monitor [note 4]
3 HEAT / 2 COOL – Including Auxiliary Heat
- Set System Type to 32HP
- Rh 24 Volt AC Power
- Rc Connected to Rh with supplied Jumper Wire
- O/B Changeover Valve [note 2]
- Y1 Compressor 1 Relay (1st stage heating/cooling)
- Y2 Compressor 2 Relay (2nd stage heating/cooling)
- AUX1/E Auxiliary Heat Relay (3rd stage heating)
- /Emergency Heat [note 5]
- E Emergency Heat Relay [note 5]
- G Fan Relay
- C 24 Volt AC Transformer Common [note 1]
- L Optional System Fault Monitor [note 4]
4 HEAT / 2 COOL – Including Auxiliary Heat
- Set System Type to 42HP
- Rh 24 Volt AC Power
- Rc Connected to Rh with supplied Jumper Wire
- O/B Changeover Valve [note 2]
- Y1 Compressor 1 Relay (1st stage heating/cooling)
- Y2 Compressor 2 Relay (2nd stage heating/cooling)
- AUX1/E Auxiliary Heat Relay 1 (3rd stage heating)
- /Emergency Heat [note 5]
- AUX2 Auxiliary Heat Relay 2 Relay (4th stage heating)
- E Emergency Heat Relay [note 5]
- G Fan Relay
- C 24 Volt AC Transformer Common [note 1]
- L Optional System Fault Monitor [note 4]
NOTES – Heat Pump Systems
- Optional 24 Volt AC common connection.
- O (cool active) or B (heat active) is selected in the Installer Settings menu.
- Install a field supplied jumper between the W2/AUX2 and W1/E/AUX1 terminals if there is no separate emergency heat relay installed.
- If the L terminal is used, the 24 Volt AC common must be connected (C terminal).
- If a separate emergency heat relay is installed, the W1/E/AUX1 terminal should have both the auxiliary heat 1 relay and emergency heat relay connected. Provide disconnect and overload protection as required.
All System Types
Additional Wiring Options
NOTE: Additional options are configured in the Installer Settings section.
S1 Indoor or Outdoor Remote Sensor [note 1]
S2 A/D Economizer Control / Dehumidification Output [note 2] H Humidification Output [note 3]
NOTES – Additional Wiring Options
- These terminals can be used to connect a Braeburn® indoor or outdoor remote sensor.
- This terminal can be used for:
- Outside air control
- Control an external dehumidifier
- Fan speed reduction
- This terminal can be used to connect an external humidifier.
- Attaching the thermostat to the sub-base
- Line up the thermostat body with the sub-base.
- Carefully push the thermostat body against the sub-base until it snaps in place.
- Insert Quick Reference Card into slot on top of thermostat.
NOTE: This thermostat ships configured as a 1H/1C conventional thermostat. Confirm installer settings. See page 10.
Quick Reference
Thermostat Display
- Room Temperature ………………….Displays the current room temperature
- Lock Mode Indicator ………………. Indicates if the thermostat is locked
- Set Temperature ……………………..Displays the current set point temperature
- Humidity Indicator………………….. Indicates when there is a call for humidity
- Fan Indicator………………………….. Indicates when the system fan is running
- Service Indicators ………………….Displays various service/maintenance information
- Time of Day ……………………………Displays the current time of day
- Program Event Indicator…………..Displays the program event
- Day of the Week………………………Displays the current day of the week
- System Status Indicator ………….Displays information about the status of the system
- Hold Mode Indicator ………………. Indicates if the thermostat is in HOLD mode
- Low Battery Indicator……………… Indicates when the batteries need to be replaced
Thermostat
- Quick Reference Instructions……Stored in slot located at top of thermostat
- SpeedBar® ……………………………… Increases or decreases settings (time, temperature, etc.)
- Reset Button ………………………….Resets current time, program and user settings
- Installer Clear Button ……………… Located on back of thermostat body – clears all settings
- Battery Compartment …………….. Located in the back of thermostat
Thermostat TouchPads
NOTE: Thermostat TouchPads are located on the left, right and bottom portions of the display screen. They are the “touch sensitive” segments used to adjust your thermostat. Depending on the equipment installed, all touch pads may not show.
- SYSTEM Selects AUTO (Heat/Cool), COOL, OFF HEAT or EMER (Emergency Heat)
- FAN Selects AUTO, ON, CIRC (Circulation) and PROG (Program) fan modes
- PROG Selects programming mode or press for 3 seconds to select SpeedSet® mode
- HOLD Enters / Exits the HOLD mode (program bypass)
- DAY/TIME Sets the current time and day of the week
- BACK Moves back in setting and programming modes
- NEXT Moves forward in setting and programming modes
- RETURN Returns to normal mode from program or settings modes
- OUTDOOR Displays the outdoor temperature if a Braeburn® outdoor sensor is installed
- HUMIDITY Displays or adjust the current humidity level
- CONFIG Enters the User and Installer settings modes
- CLEAN Enters a brief screen cleaning mode
Installer Settings
The Installer Settings must be properly configured in order for this thermostat to operate correctly. The Installer Settings are menu driven. The portion of these settings that do not apply to your setup will be skipped. These settings are indicated below with comments. More detail on each setting follows this table.
- Touch and hold down the SYSTEM and CONFIG TouchPads for 3 seconds.
- Release both buttons and the first installer setting will be displayed.
- Change settings as required using the UP or DOWN portion of the SpeedBar®.
- Touch NEXT or BACK to move to the next or previous setting, touch RETURN to exit.
- No. Installer Setting Factory Setting Comments (Notes follow this table) Default Options (More information follows this table)
- Residential or RES RES Select for Residential profile or Commercial Profile COMM Select for Commercial profile
- Programming Mode 7 PROG 7 PROG Select for 7 day programming mode [note 1] 52 PROG Select for 5-2 day programming mode NO PROG Select for non-programmable mode
- Clock Format 12 HR 12 HR Select for 12 hour clock 24 HR Select for 24 hour clock
- Temperature Scale F DEG F DEG Select for Fahrenheit display C DEG Select for Celsius display
- Auto Changeover oF AUTO oF AUTO Disables Auto Changeover mode ON AUTO Enables Auto Changeover mode 11CONV Select for 1H/1C Conventional system 22CONV Select for 2H/2C Conventional system 32CONV Select for 3H/2C Conventional system
- System Type 11CONV 11HP Select for 1H/1C Heat Pump system 22HP Select for 2H/2C Heat Pump system 32HP Select for 3H/2C Heat Pump system 42HP Select for 4H/2C Heat Pump system
- 1st Stage Differential 0.5 DIF1 0.5, 1.0 or Select a 1st stage temperature differential of .5°, 2.0 DIF1 1° or 2° F (.25°, .5° or 2° C)
- 2nd Stage Differential 2.0 DIF2 1.0, 2.0, 3.0, Select a 2nd stage temperature differential of 1°, [note 2] 4.0, 5.0 or 2°, 3°, 4°, 5° or 6° F (.5°, 1°, 1.5°, 2°, 2.5° or 3° C) 6.0 DIF2
- 3rd Stage Differential 2.0 DIF3 1.0, 2.0, 3.0, Select a 3rd stage temperature differential of 1°, 2°, [note 2] 4.0, 5.0 or 3°, 4°, 5° or 6° F (.5°, 1°, 1.5°, 2°, 2.5° or 3°C) 6.0 DIF3
- 4th Stage Differential 2.0 DIF4 1.0, 2.0, 3.0, Select a 4th stage temperature differential of 1˚, [note 2] 4.0, 5.0 or 2°, 3°, 4°, 5° or 6° F (.5°, 1°, 1.5°, 2°, 2.5° or 3° C) 6.0 DIF4
- 1st Stage Fan Control HG FAN 1 HG FAN 1 Select for 1st stage Gas heating [note 3] HE FAN 1 Select for 1st stage Electric heating
- Emergency Heat] HE EMER HE EMER Select for Electric Emergency Heat Fan Control [note 4] HG EMER Select for Gas Emergency Heat
- Reversing Valve REVO REVO Select for cool active Reversing Valve (O terminal) (O/B Terminal) [note 5] REVB Select for heat active Reversing Valve (B terminal)
- Fossil Fuel AE AUX AE AUX Select for Electric Auxiliary heat (with compressor) Backup Heat [note 4] AG AUX Select for Gas Auxiliary heat (without compressor)
- Compressor Power Outage oF CPOP oF CPOP Disables Power Outage Lockout Delay Protection [notes 3, 6] on CPOP Enables Power Outage Lockout Delay
- AC Power Interrupt AC oF MONR AC oF MONR Disables AC Power Interrupt Warning Warning [note 6] AC on MONR Enables AC Power Interrupt Warning
- Compressor Short 5 CSCP 5, 4, 3, 2 or Select a compressor short cycle protection delay of 5, Cycle Protection 0 CSCP 4, 3, 2 or 0 minutes
- Residual Cooling 60 FAN 90, 60, 30 Select a Residual Cooling Fan Delay of 90, 60, Fan Delay or 0 FAN 30 or 0 seconds.
- Circulating Fan Lock oF CIRC oF CIRC Disables Circulating Fan Lock mode on CIRC Enables Circulating Fan Lock mode
- Adaptive Recovery oF REC oF REC Disables Adaptive (early) Recovery mode Mode (ARM™) [note 7] on REC Enables Adaptive (early) Recovery mode
- Indoor Remote Sensor I SENS I SENS Temperature is sensed from thermostat only. Control* [note 8] E SENS Temperature is sensed from remote sensor only. A SENS Temperature is combined with the thermostat and the remote sensor.
- Lockout Security Level 2 LOCK 2 LOCK If locked – Complete lockout is enabled 1 LOCK If locked – Partial lockout is enabled (SpeedBar® is still functional)
- Humidification OFF OFF Disables Humidification DEP Enables Dependent Humidification IND Enables Independent Humidification
- Auto Humidity Set AUTO AUTO Enables automatic humidity control based on Point Limit [notes 9, 12] outdoor temperature. MAN Enables manual humidity control from thermostat.
- Dehumidification OFF OFF Disables Dehumidification DEP Enables Dependent Dehumidification IND Enables Independent Dehumidification
- Dehumidification Over 1.0 LIM 1.0, 2.0 or Select a dehumidification over cooling limit of 1.0°, 2.0° Cooling Limit [note 10] 3.0 LIM or 3.0° F (.5°, 1.0° or 1.5° C)
- Dehumidification OFF OFF Disables Dehumidification Terminal (D) Terminal (D) Output NI Selects normally inactive relay (N/O) NA Selects normally active relay (N/C)
- Auto Changeover 3 BAND 2, 3, 4 or 5 Select a Dead Band of 2°, 3°, 4° or 5° F Dead Band [note 11] BAND (1°, 2° or 3° C) for Auto Changeover mode.
- Compressor Balance NO BALC NO BALC Disables Balance Points Point [notes 4, 12] 15-50 BALC Select a Compressor Balance Point of 15°- 50 °F (-9°-10° C)
- Auxiliary Heat Balance NO BALA NO BALA Disables Balance Points Point [notes 4, 12] 70-40 BALA Select a Auxiliary Heat Balance Point of 70°- 40° F (21°- 4° C)
- Outside Air Intake OA NONE OA NONE Disables Outside Air Intake option (A Terminal) [note 13] OA ECON Enables Outside Air Intake (Economizer Mode) OA TOD Enables Outside Air Intake (Time of Day Mode)
- Heat Set Point Upper Limit 90LIM 90-60 LIM Select a Heat Set Point Upper Limit of 90°-60° F (32°-10° C)
- Cool Set Point Lower Limit 45LIM 45-80 LIM Select a Cool Set Point Lower Limit of 45°-80° F (7°-27° C)
- When a Braeburn® outdoor sensor is connected, the thermostat automatically recognizes it.
NOTE: Additional options such as Service Monitors, Setting the lock code, audible tone, etc. are located in the User Settings – See User manual for information on setting these options.
NOTES – Installer Settings
- Only available if Residential profile was selected in option 1.
- Only available if a 2, 3 or 4 stage system type was selected in option 6.
- Only available if a Conventional system was selected in option 6.
- Only available if a 2, 3 or 4 stage Heat Pump system was selected in option 6.
- Only available if a Heat Pump system was selected in option 6.
- Only available if the 24 Volt AC common wire is connected to the C terminal.
- Only available if a programmable profile was selected in option 2.
- Only available if a Braeburn® indoor remote sensor was connected.
- Only available if humidification was enabled in option 23.
- Only available if dependent dehumidification was enabled in option 25.
- Only available if auto changeover was enabled in option 5.
- Only available if a Braeburn outdoor sensor was connected.
- Only available if Commercial profile was selected in option 1
Detailed Explanation of Installer Settings (also see NOTES above):
- Profile – Selects a residential (RES) or commercial (COMM) profile. If residential is selected, 4 programming events per day are available. If commercial is selected, 2 event, 7 day programming is available.
- Programming Mode [note 1] – Selects the programming mode, either full 7 day or 5-2 day (weekday/ weekend) programming or non programmable.
- Clock Type – Selects either a 12 hour or 24 hour clock.
- Temperature Scale – Selects a temperature scale of either °F or °C.
- Auto Changeover – Selects auto changeover on or off. When auto changeover mode is enabled and selected, the system automatically switches between heating and cooling modes.
NOTE: Also see “Auto Changeover Dead Band” in option 28. - System Type – Selects the system type for your installation. NOTE: Changes made to this option will reset options 7 through 15 back to their default values dependant on the system type.
- 1st Stage Differential – Selects a 1st stage temperature differential.
- 2nd Stage Differential [note 2] – Selects a 2nd stage temperature differential.
- 3rd Stage Differential [note 2] – Selects a 3rd stage temperature differential.
- 4th Stage Differential [note 2] – Selects a 4th stage temperature differential.
- 1st Stage Fan Control [note 3] – Selects a 1st stage fan control of either gas or electric heat.
- Emergency Heat Fan Control [note 4] – Selects emergency heat fan control of either gas or electric heat.
- Reversing Valve [Note 5] – Selects the output state of the O/B terminal. Select O for this terminal to be active in the cool mode or select B for this terminal to be active in the heat mode.
- Auxiliary Fossil Fuel Heat Pump Control [note 4] – When set to electric (AE AUX), both the compressor (1st stage) and auxiliary stage(s) will run when a call for auxiliary heat is made. When set to gas (AG AUX), the compressor stage(s) will be locked out one minute after a call for auxiliary heat. NOTE: This option can be overridden if setting an auxiliary heat balance point in Option 30.
- Compressor Power Outage Protection [notes 3, 6] – Selects power outage protection on or off. When enabled, this thermostat will provide cold weather compressor protection by locking out the compressor stage(s) of heating for a period of time after a power outage greater than 60 minutes.
- AC Power Interrupt Warning [note 6] – When enabled, the thermostat will display an outage warning when AC power to the thermostat is lost.
- Short Cycle Protection – Selects the number of minutes the cooling compressor will be locked out after turning off. This short cycle protection is also active in the heat mode if a heat pump system was selected in Option 6.
- Residual Cooling Fan Delay – Selects a delay for the system fan after the cooling compressor has turned off. This delay will help remove the remaining cool air out of the ductwork providing additional efficiency.
- Circulating Fan Lock – When enabled, the only user fan options available are ON and CIRC (Circulation). The AUTO option is not available with this option enabled.
- Adaptive Recovery Mode (early recovery) [note 7] – Enables or disables the ARMTM (adaptive recovery mode) feature. During ARM, room temperature is recovered by turning on the heating or cooling before the end of the set back period. The set point temperature is changed to that of the upcoming program temperature.
- Indoor Remote Sensor Control [note 8] – If a Braeburn® indoor remote sensor is connected during installation, the thermostat will automatically detect the sensor. When an indoor sensor is detected, you may select between thermostat only (I SENS), remote sensor only (E SENS) or combining the thermostat and the remote sensor (A SENS). NOTE: This option does not apply to a Braeburn outdoor sensor. When an outdoor sensor is connected the thermostat automatically recognizes it and no further configuration is necessary.
- Lockout Security Level – Selects the level of keypad lockout when the thermostat is locked. Level 2 locks the entire thermostat (including the front reset button). Level 1 locks everything except the SpeedBar® allowing for up and down temperature adjustment. NOTE: The lock code is set in the User Settings mode (see User Manual).
- Humidification Mode – For use with an external humidifier. Selects between disabling humidification (OFF), dependant control (DEP) or independent control (IND). The DEP setting controls humidification only during a call for heating. The IND setting allows humidification output in the heat mode, but does not require a call for heating. NOTE: It is recommended that the IND setting only be used with systems designed for low air temperature humidification such as steam humidification. Always ensure the heat exchanger or other system parts are not exposed to excess water from condensation or other sources. When there is any doubt, use the OFF or DEP setting.
- Auto Humidity Set Point Limit [notes 9, 11] – Select between turning the automatic humidity set point limit to auto (AUTO) or manual (MAN). When AUTO is selected, humidity control is provided automatically based on the outdoor temperature. Selecting MAN allows you to manually control the level of humidity.
- Dehumidification – Selects between dehumidification disabled (OFF), dependent dehumidification (DEP) or independent dehumidification (IND). (DEP) If the humidity level is above the humidity set point, cooling stays on until the humidity level drops below the set point or when the over cooling limit is reached in installer setting 26. (IND) For use with an external dehumidifier. When the humidity level rises above the dehumidification set point, both the G (Fan) and D terminals are activated. Installer setting 27 sets if D is normally active or inactive.
- Dehumidification Over Cooling Limit [note 10] – Select the number of degrees the system is allowed to over cool in attempting to reduce humidity
- Dehumidification Terminal (D) Output – Select normally inactive relay (NI) or a normally active (NA) relay. This setting can be used in independent or dependent modes and can also be used for dehumidification fan speed control.
- Auto Changeover Dead Band [note 11] – When Auto Changeover mode is enabled in option 5 and selected, the system automatically switches between heating and cooling when the room temperature meets the normal criteria for either a heating or cooling call. There is a forced separation (dead band) between the heating and cooling set points so the systems do not work against each other. This option selects the amount of this dead band in degrees with the default being 3° F.
Dehumidification
Over Cooling Limit
Allowable
Dead Band
Dehumidification
not enabled
1˚ F (.5˚ C)
2˚ F (1.0˚ C)
3˚ F (1.5˚ C)
2, 3, 4 or 5˚ F (1, 2 or 3˚ C)
3, 4 or 5˚ F (1, 2 or 3˚ C)
4 or 5˚ F (2 or 3˚ C)
5˚ F (3˚ C)
- Compressor Balance Point [notes 4, 12] – Locks out the use of the compressor heat stage when the outside air temperature is less than the selected setting of 15° F to 50° F (-9° C to 10° C).
- Auxiliary Heat Balance Point [notes 4, 12] – Locks out the use of the auxiliary heat stage when the outside air temperature exceeds the selected setting of 70° F to 40° F (21° C to 4° C). NOTE: This balance point overrides the fossil fuel compressor lockout in option 14. If this option is set to gas and the outdoor
- Outside Air Intake [note 13] – Selects economizer control options. Select between disabled (NONE), economizer mode (ECON) and time of day (TOD) mode.
Time Step / Override Cooling Call
Occupied YES or NO ON ON OFF
YES ON OFF OFF
NO OFF OFF OFF
Override YES or NO ON ON OFF
Time Step / Override Heating Call
Occupied YES or NO ON ON OFF
YES OFF OFF OFF
NO OFF OFF OFF
Override YES or NO ON ON OFF
- Heat Set Point Upper Limit – Selects the heating set point upper adjustment limit.
- Cool Set Point Lower Limit – Selects the cooling set point lower adjustment limit.
System Testing
Warning Read Before Testing
- Do not short (or jumper) across terminals on the gas valve or at the heating or cooling system control board to test the thermostat installation. This could damage the thermostat and void the warranty.
- Do not select the COOL mode of operation if the outside temperature is below 50º F (10º C). This could possibly damage the controlled cooling system and may cause personal injury.
- This thermostat includes an automatic compressor protection feature to avoid potential damage to the compressor from short cycling. When testing the system, make sure to take this delay into account.
NOTE: The compressor delay can be bypassed by pressing the reset button on the front of the thermostat. All user settings will be returned to factory default, however all Installer settings will remain as originally programmed in section 4.
- Touch the SYSTEM TouchPad until the thermostat is in HEAT mode.
- Using the SpeedBar® raise the set temperature a minimum of 3 degrees above the current room temperature. The system should start within a few seconds. With a gas heating system, the fan may not start right away.
- Touch SYSTEM until the thermostat is in the OFF mode. Allow the heating system to fully shut down.
- Touch SYSTEM until the thermostat is in the COOL mode.
- Using the SpeedBar lower the set temperature a minimum of 3 degrees below the current room temperature. The system should start within a few seconds (unless compressor short cycle protection is active – See note above).
- Touch SYSTEM until the thermostat is in the OFF mode. Allow the cooling system to fully shut down.
- Touch FAN until the thermostat is in FAN ON mode. The system fan should start within a few seconds.
- Touch FAN until the thermostat is in FAN AUTO mode. Allow the system fan to turn off.
- If the thermostat is controlling auxiliary equipment such as a humidifier, economizer, etc., adjust the thermostat settings to test these devices.
Limited Warranty
When installed by a professional contractor, this product is backed by a 5 year limited warranty. Limitations apply. For limitations, terms and conditions, you may obtain a full copy of this warranty:
- Visit us online: www.braeburnonline.com/warranty
- Phone us: 866.268.5599
- Write us: Braeburn Systems LLC 2215 Cornell Avenue Montgomery, IL 60538