Panasonic-CS-LU9ZKA-Air-Conditioner-FEATURE

Panasonic CS-LU9ZKA Air Conditioner Operating Instructions

Panasonic-logo

Panasonic CS-LU9ZKA Air Conditioner Operating Instructions

Panasonic-CS-LU9ZKA-Air-Conditioner-IMG

Quick Guide

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig1

Accessories

  • Remote control
  • AAA or R03 batteries × 2
  • Remote control holder
  • Screws for remote control holder × 2

Basic operation

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig2

Safety Precautions

To prevent personal injury, injury to others or property damage, please comply with the following: Incorrect operation due to failure to follow instructions below may cause harm or damage, the seriousness of which is classifi ed as below: This appliances is not intended for accessibility by the general public.

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig3

The instructions to be followed are classified by the following symbols:

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig4

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig8WARNING

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig5

Remote control

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig6Do not allow infants and small children to play with the remote control to prevent them from accidentally swallowing the batteries.

Power supply

 

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig7

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig8CAUTION

Indoor unit and outdoor unit

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig6Do not wash the indoor unit with water, benzine, thinner or scouring powder to avoid damage or corrosion at the unit. Do not use for preservation of precise equipment, food, animals, plants, artwork or other objects. This may cause quality deterioration, etc. Do not use any combustible equipment in front of the airflow outlet to avoid fi re propagation. Do not expose plants or pet directly to airflow to avoid injury, etc.  Do not touch the sharp aluminium fin, sharp parts may cause injury. Panasonic-CS-LU9ZKA-Air-Conditioner-Fig10 Do not switch ON the indoor unit when waxing the floor. After waxing, aerate the room properly before operating the unit. Do not install the unit in oily and smoky areas to prevent damage to the unit. Do not dismantle the unit for cleaning purpose to avoid injury. Do not step onto an unstable bench when cleaning the unit to avoid injury. Do not place a vase or water container on the unit. Water may enter the unit and degrade the insulation. This may cause an electric shock. Do not open window or door for long time during operation, it may lead to inefficient power usage and uncomfortable temperature changes.
Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Prevent water leakage by ensuring drainage pipe is:
– Connected properly,
– Kept clear of gutters and containers, or
– Not immersed in water After a long period of use or use with any combustible equipment, aerate the room regularly. After a long period of use, make sure the installation bolts and nuts does not deteriorate to prevent the unit from falling down.

Remote control

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig6Do not use rechargeable (Ni-Cd) batteries. It may damage the remote control.
Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9To prevent malfunction or damage of the remote control:

  • Remove the batteries if the unit is not going to be used for a long period of time.
  • New batteries of the same type must be inserted following the polarity stated.

Power supply

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig6Do not disconnect the plug by pulling the cord to prevent electric shock.

nanoe™-G generator

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig6Do not touch the sharp pin which may cause injury.

Safety Precautions

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig8WARNING

This appliance is filled with R32 (mildly flammable refrigerant). If the refrigerant is leaked and exposed to an external ignition source, there is a risk of fi re.

Indoor unit and outdoor unit

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9The appliance shall be installed, and/or operated in a room with fl oor area larger than Amin (m²) and keep away from ignition sources, such as heat/sparks/open flame or hazardous areas such as gas appliances, gas cooking, reticulated gas supply systems or electric cooking appliances, etc. (Refer to Table A of Installation instructions table for Amin (m²)) Be aware that refrigerant may not contain an odour, highly recommended to ensure suitable flammable refrigerant gas detectors are present, operating and able to warn of a leak. Keep any required ventilation openings clear of obstruction.

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig6Do not pierce or burn as the appliance is pressurized. Do not expose the appliance to heat, fl ame, sparks, or other sources of ignition. Else it may explode and cause injury or death.

Precaution for using R32 refrigerant

The basic installation work procedures are the same as conventional refrigerant (R410A, R22) models.
Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Since the working pressure is higher than that of refrigerant R22 models, some of the piping and installation and service tools are special. Especially, when replacing a refrigerant R22 model with a new refrigerant R32 model, always replace the conventional piping and flare nuts with the R32 and R410A piping and flare nuts on the outdoor unit side. For R32 and R410A, the same flare nut on the outdoor unit side and pipe can be used. The mixing of different refrigerants within a system is prohibited. Models that use refrigerant R32 and R410A have a different charging port thread diameter to prevent erroneous charging with refrigerant R22 and for safety. Therefore, check beforehand. [The charging port thread diameter for R32 and R410A is 1/2 inch.]

  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Must always ensure that foreign matter (oil, water, etc.) does not enter the piping. Also, when storing the piping, securely seal the opening by pinching, taping, etc. (Handling of R32 is similar to R410A.)
  • Operation, maintenance, repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of flammable refrigerants and as recommended by the manufacturer. Any personnel conducting an operation, servicing or maintenance on a system or associated parts of the equipment should be trained and certified.
  • Any part of refrigerating circuit (evaporators, air coolers, AHU, condensers or liquid receivers) or piping should not be located in the proximity of heat sources, open flames, operating gas appliance or an operating electric heater.
  • The user/owner or their authorised representative shall regularly check the alarms, mechanical ventilation and detectors, at least once a year, where as required by national regulations, to ensure their correct functioning.
  • A logbook shall be maintained. The results of these checks shall be recorded in thelogbook.
  • In case of ventilations in occupied spaces shall be checked to confirm no obstruction.
  • Before a new refrigerating system is put into service, the person responsible for placing the system in operation should ensure that trained and certified operating personnel are instructed on the basis of the instruction manual about the construction, supervision, operation and maintenance of the refrigerating system, as well as the safety measures to be observed, and the properties and handling of the refrigerant used.
  • The general requirement of trained and certified personnel are indicated as below:
  • Knowledge of legislation, regulations and standards relating to flammable refrigerants; and,
  • Detailed knowledge of and skills in handling flammable refrigerants, personal protective equipment, refrigerant leakage prevention, handling of cylinders, charging, leak detection, recovery and disposal; and,
  • Able to understand and to apply in practice the requirements in the national legislation, regulations and Standards; and,
  • Continuously undergo regular and further training to maintain this expertise.
  • Air-conditioner piping in the occupied space shall be installed in such a way to protect against accidental damage in operation and service.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Precautions shall be taken to avoid excessive vibration or pulsation to refrigerating piping.
  • Ensure protection devices, refrigerating piping and fittings are well protected against adverse environmental effects (such as the danger of water collecting and freezing in relief pipes or the accumulation of dirt and debris).
  • Expansion and contraction of long runs piping in refrigerating systems shall be designed and installed securely (mounted and guarded) to minimize the likelihood hydraulic shock damaging the system.
  • Protect the refrigerating system from accidental rupture due to moving furniture or reconstruction activities.
  • To ensure no leaking, field-made refrigerant joints indoors shall be tightness tested. The test method shall have a sensitivity of 5 grams per year of refrigerant or better under a pressure of at least 0.25 times the maximum allowable pressure (>1.04 MPa, max 4.15 MPa). No leak shall be detected.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Installation (Space)
  • Product with flammable refrigerants, shall be installed according to the minimum room area, Amin (m²) mentioned in Table A of the Installation Instructions.
  • In case of fi eld charge, the effect on refrigerant charge caused by the different pipe length has to be quantified, measured and labelled.
  • Must ensure the installation of pipe-work shall be kept to a minimum. Avoid use dented pipe and do not allow acute bending.
  • Must ensure that pipe-work shall be protected from physical damage.
  • Must comply with national gas regulations, state municipal rules and legislation. Notify relevant authorities in accordance with all applicable regulations.
  • Must ensure mechanical connections be accessible for maintenance purposes.
  • In cases that require mechanical ventilation, ventilation openings shall be kept clear of obstruction.
  • When disposal of the product, do follow to the precautions in #12 and comply with national regulations.
  • Always contact to local municipal offices for proper handling.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Servicing
  • Service personnel
  • The system is inspected, regularly supervised and maintained by a trained and certified service personnel who is employed by the person user or party responsible.
  • Ensure the actual refrigerant charge is in accordance with the room size within which the refrigerant containing parts are installed.
  • Ensure refrigerant charge not to leak.
  • Any qualified person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry-accredited assessment authority, which authorizes their competence to handle refrigerants safely in accordance with an industry recognized assessment specification.
  • Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants.
  • Servicing shall be performed only as recommended by the manufacturer.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Work
  • Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the precautions in #2-2 to #2-8 must be followed before conducting work on the system.
  • Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapour being present while the work is being performed.
  • All maintenance staff and others working in the local area shall be instructed and supervised on the nature of work being carried out.
  • Avoid working in confined spaces. Always ensure away from source, at least 2 meter of safety distance, or zoning of free space area of at least 2 meter in radius.
  • Wear appropriate protective equipment, including respiratory protection, as conditions warrant.
  • Keep all sources of ignition and hot metal surfaces away.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Checking for presence of refrigerant
  • The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres.
  • Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. non sparking, adequately sealed or intrinsically safe.
  • In case of leakage/spillage happened, immediately ventilate area and stay upwind and away from spill/release.
  • In case of leakage/spillage happened, do notify persons down wind of the leaking/ spill, isolate immediate hazard area and keep un authorised personnel out.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Presence of fi re extinguisher
  • If any hot work is to be conducted on the refrigerating equipment or any associated parts, appropriate fire extinguishing equipment shall be available at hand.
  • Have a dry powder or CO2 fi re extinguisher adjacent to the charging area.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9No ignition sources
  • No person carrying out work in relation to a refrigerating system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. They must not be smoking when carrying out such work.
  • All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which flammable refrigerant can possibly be released to the surrounding space.
  • Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks.
  • No Smoking” signs shall be displayed.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Ventilated area
  • Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work.
  • A degree of ventilation shall continue during the period that the work is carried out.
  • The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Checks to the refrigerating equipment
  • Where electrical components are being changed, they shall be fi t for the purpose and to the correct specification.
  • At all times the manufacturer’s maintenance and service guidelines shall be followed.
  • If in doubt consult the manufacturer’s technical department for assistance.
  • The following checks shall be applied to installations using flammable refrigerants.
  • The actual refrigerant charge is in accordance with the room size within which the refrigerant containing parts are installed.
  • The ventilation machinery and outlets are operating adequately and are not obstructed.
  • If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant.
  • Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected.
  • Refrigerating pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are properly protected against being so corroded.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Checks to electrical devices
  • Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures.
  • Initial safety checks shall include but not limit to:-
  • That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking.
  • That there no live electrical components and wiring are exposed while charging, recovering or purging the system.
  • That there is continuity of earth bonding.
  • At all times the manufacturer’s maintenance and service guidelines shall be followed.
  • If in doubt consult the manufacturer’s technical department for assistance.
  • If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with.
  • If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used.
  • The owner of the equipment must be informed or reported so all parties are advised thereinafter.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Repairs to sealed components
  • During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc.
  • If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
  • Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc.
  • Ensure that apparatus is mounted securely.
  • Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of
    flammable atmospheres.
  • Replacement parts shall be in accordance with the manufacturer’s specifications.

NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to working on them.

  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Repair to intrinsically safe components
  • Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use.
  • Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere.
  • The test apparatus shall be at the correct rating.
  • Replace components only with parts specified by the manufacturer. Unspecified parts by manufacturer may result ignition of refrigerant in the atmosphere from a leak.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Cabling
  • Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects.
  • The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Detection of fl ammable refrigerants
  • Under no circumstances shall potential sources of ignition be used in the searching or detection of refrigerant leaks.
  • A halide torch (or any other detector using a naked flame) shall not be used.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9The following leak detection methods are deemed acceptable for all refrigerant systems
  • No leaks shall be detected using detection equipment with sensitivity to detect leakage of 5g/year of refrigerant or better under a  pressure of at least 0.25 times the maximum allowable pressure (>1.04 MPa, max 4.15 MPa), for example, a universal sniffer.
  • Electronic leak detectors may be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re calibration. (Detection equipment shall be calibrated in a refrigerant-free area.)
  • Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used.
  • Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed.
  • Leak detection fluids are also suitable for use with most refrigerants, for example, bubble method and fluorescent method agents. The use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.
  • If a leak is suspected, all naked flames shall be removed/extinguished.
  • If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. The precautions in #8 must be followed to remove the refrigerant.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Removal and evacuation
  • When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to: remove refrigerant -> purge the circuit with inert gas -> evacuate -> purge with inert gas -> open the circuit by cutting or brazing.
  • The refrigerant charge shall be recovered into the correct recovery cylinders.
  • The system shall be purged with OFN to render the appliance safe.
  • This process may need to be repeated several times.
  • Compressed air or oxygen shall not be used for this task.
  • Purging shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum.
  • This process shall be repeated until no refrigerant is within the system.
  • When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place.
  • This operation is absolutely vital if brazing operations on the pipe work are to take place.
  • Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and there is ventilation available.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Charging procedures
  • In addition to conventional charging procedures, the following requirements shall be followed.
  • Ensure that contamination of different refrigerants does not occur when using charging equipment.
  • Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
  • Cylinders shall be kept in an appropriate position according to the instructions.
  • Ensure that the refrigerating system is earthed prior to charging the system with refrigerant.
  • Label the system when charging is complete (if not already).
  • Extreme care shall be taken not to over fill the refrigerating system.
  • Prior to recharging the system it shall be pressure tested with OFN (refer to #7).
  • The system shall be leak tested on completion of charging but prior to commissioning.
  • A follow up leak test shall be carried out prior to leaving the site.
  • Electrostatic charge may accumulate and create a hazardous condition when charging and discharging the refrigerant. To avoid fi re or explosion, dissipate static electricity during transfer by grounding and bonding containers and equipment before charging/discharging.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Decommissioning
  • Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its details.
  • It is recommended good practice that all refrigerants are recovered safely.
  • Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant.
  • It is essential that electrical power is available before the task is commenced.
  • Become familiar with the equipment and its operation.
  • Isolate system electrically.
  • Before attempting the procedure ensure that:
  • mechanical handling equipment is available, if required, for handling refrigerant cylinders;
  • all personal protective equipment is available and being used correctly;
  • the recovery process is supervised at all times by a competent person;
  • recovery equipment and cylinders conform to the appropriate standards.
  • Pump down refrigerant system, if possible.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
  • Make sure that cylinder is situated on the scales before recovery takes place.
  • Start the recovery machine and operate in accordance with instructions.
  • Do not over fill cylinders. (No more than 80 % volume liquid charge).
  • Do not exceed the maximum working pressure of the cylinder, even temporarily.
  •  When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off.
  • Recovered refrigerant shall not be charged into another refrigerating system unless it has been cleaned and checked.
  • Electrostatic charge may accumulate and create a hazardous condition when charging or discharging the refrigerant. To avoid fi re or explosion, dissipate static electricity during transfer by grounding and bonding containers and equipment before charging/discharging.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Labelling
  • Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant.
  • The label shall be dated and signed.
  • Ensure that there are labels on the equipment stating the equipment contains fl ammable refrigerant.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9Recovery
  • When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.
  • When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed.
  • Ensure that the correct number of cylinders for holding the total system charge are available.
  • All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant).
  • Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order.
  • Recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
  • Panasonic-CS-LU9ZKA-Air-Conditioner-Fig9The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants.
  • In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition.
  • Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.
  • The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged.
  • Do not mix refrigerants in recovery units and especially not in cylinders.
  • If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant.
  • The evacuation process shall be carried out prior to returning the compressor to the suppliers.
  • Only electric heating to the compressor body shall be employed to accelerate this process.
  • When oil is drained from a system, it shall be carried out safely.

How to Use

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig11

To adjust airflow direction

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig12

Upper direction:

  • Do not adjust the flap by hand.
  • For details operation, refer “To Learn More….”

Lateral direction:

  • For lateral direction, it is manually adjustable as shown.

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig13

To adjust FAN SPEED and QUIET condition

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig14

FAN SPEED:

  • When AUTO FAN is selected, the fan speed is adjusted automatically according to the operation mode.

QUIET:

  • This operation reduces airfl ow noise.
To switch between POWERFUL/ECO

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig15

POWERFUL:
To reach the desired temperature quickly

  • This operation is automatically stop after 20 minutes.

ECO:

  • To reduce power consumption for better energy saving without sacrificing comfort.
To enjoy fresher and cleaner environment

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig16

  • This operation combines both nanoe™X and nanoe™-G
    (nanoe™ TECHNOLOGY).
  • nanoe™ TECHNOLOGY automatically starts when the unit is turned on.
  • Press Panasonic-CS-LU9ZKA-Air-Conditioner-Fig17to turn ON or OFF this operation manually.
  • This operation can be activated even when the unit is OFF. Note that the flap and fan speed will operate according to the remote control setting.
  • If a power failure occurs during this operation, this operation resumes immediately when power resumes.
To connect to a network

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig17

  • For Wireless LAN Module operation setup, please refer to Setup Instructions Manual.
To maximise comfort while sleeping

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig18

  • This operation provides you with a comfortable environment while sleeping. It will automatically adjust the sleep pattern temperature during the activation period.
  • The indoor unit indicator will dim when this operation is activated. This is not applicable if the indicator brightness has been manually dimmed.
  • This operation is incorporated with the activation timer (0.5, 1, 2, 3, 4, 5, 6, 7, 8 or 9 hours).
  • This operation can be set together with timer. Sleep operation has the priority over OFF timer.
  • This operation can be cancelled by pressing the respective button until the sleep timer reaches 0.0h.

To set the timer

You can set the timer to turn on and off the unit at 2 different preset time.

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig19

  • To cancel the timer, press Panasonic-CS-LU9ZKA-Air-Conditioner-Fig20orPanasonic-CS-LU9ZKA-Air-Conditioner-Fig21  to select the respective setting Panasonic-CS-LU9ZKA-Air-Conditioner-Fig24orPanasonic-CS-LU9ZKA-Air-Conditioner-Fig24 , then pressPanasonic-CS-LU9ZKA-Air-Conditioner-Fig22 .
  • If the timer has been cancelled manually or due to power failure, you can restore the timer again. Press Panasonic-CS-LU9ZKA-Air-Conditioner-Fig20or Panasonic-CS-LU9ZKA-Air-Conditioner-Fig21 to select the respective setting Panasonic-CS-LU9ZKA-Air-Conditioner-Fig24orPanasonic-CS-LU9ZKA-Air-Conditioner-Fig24 , then pressPanasonic-CS-LU9ZKA-Air-Conditioner-Fig23  .
  • The nearest timer setting is displayed and will activate in sequence.
  • The timer operation follows the clock setting on the remote control and will repeat daily when timer has been set. For clock setting, refer to Quick Guide.

Note

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig25

To Learn More

Operation mode

AUTO : The POWER indicator blinks at the initial stage. The unit will select an operation mode depending on the room temperature.
COOL : Provides effi cient comfort cooling to suit your needs.
DRY : Operates at low fan speed for a gentle cooling operation.

Energy saving temperature setting

You may save energy when operating the unit within the recommended temperature range. COOL : 26.0 °C ~ 28.0 °C / 79 °F ~ 82 °F.

Air flow direction

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig26In COOL/DRY mode:
The horizontal flap is fixed at middle position setting. Once the temperature is achieved, the horizontal flap swings up/down automatically.
Panasonic-CS-LU9ZKA-Air-Conditioner-Fig27In COOL/DRY mode:
The horizontal flap swings up/down automatically.

Auto restart control

When power is resumed after a power failure, the operation will restart automatically with the last operation mode and airflow direction.

  • This control is not applicable when TIMER is set.
nanoe™X Inside Cleaning

Depending on the unit’s accumulated operation time, the nanoe™X may be activated only once a day after the unit is turned off standby mode. During the nanoe™X Inside Cleaning operation, the flap will open slightly with low fan speed operation for 2.5 hours if the unit was in COOL/DRY mode, and 2 hours if the unit was in nanoe™ TECHNOLOGY, before the unit is turned off. This is to remove viruses/bacteria from the surroundings. The Inside Cleaning operation is complete when the fan stops and the flap closes. Do not turn off the power supply during this operation. After a power failure, this operation will not resume.

Operating conditions

Use this air conditioner in the temperature range indicated in the table.

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig28

Cleaning the Air Conditioner

Cleaning has to be carried out at regular intervals to ensure the unit is at optimal performance. A dirty unit may cause malfunction and you may retrieve “H 99” error code. Consult an authorized dealer.

  • Before cleaning, switch off the power supply and unplug the unit.
  • Do not touch the aluminum fi n as the sharp parts may cause injury.
  • Do not use benzine, thinner or scouring powder.
  • Use soap ( pH 7) or neutral household detergent only.
  • Do not use water hotter than 40 °C / 104 °F.

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig29

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig30

Troubleshooting

The following symptoms do not indicate malfunction.

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig31

When
  • The remote control is missing or a malfunction has occurred

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig32

  • Raise the front panel.
  • Press AUTO OFF/ON once to use in AUTO mode.
  • Press AUTO OFF/ON hold for 5 seconds until you hear 1 beep, then release to use in forced COOL mode. (This operation shall be performed by service personnel)
  • Press AUTO OFF/ON again to turn off the unit.
  • The indicators are too bright
  • To dim or restore the indicators’ brightness on the unit, press Panasonic-CS-LU9ZKA-Air-Conditioner-Fig33on the remote for 5 seconds.
  • Conducting a seasonal inspection after extended period of non-use
  • Check the batteries.
  • Check that there is no obstruction around the air inlets and outlet vents.
  • Use AUTO OFF/ON on the unit to select COOL mode. For details, refer “The remote control is missing or a malfunction has occurred” above. After 15 minutes of operation, it is normal to have the following temperature difference between the air inlet and outlet vents: COOL: ≥ 8 °C / 14.4 °F
  • The units will not be used for an extended period
  • Activate nanoe™ TECHNOLOGY mode for 2~3 hours to remove any moisture left in the internal parts thoroughly. This is to prevent mould growth.
  • Turn off the power supply and unplug the unit.
  • Remove the batteries from the remote control.

NON SERVICEABLE CRITERIAS

TURN OFF THE POWER SUPPLY AND UNPLUG THE UNIT. Then consult an authorized dealer in the following conditions:

  • Abnormal noise during operation.
  • Water/foreign particles have entered the remote control.
  • Water is leaking from the indoor unit.
  • The circuit breaker switches off frequently.
  • The power cord becomes unnaturally warm.
  • The switches or buttons are not functioning properly.
How to retrieve error codes

If the unit stops and the TIMER indicator blinks, use the remote control to retrieve the error code.

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig34

Information

Panasonic-CS-LU9ZKA-Air-Conditioner-Fig35

REFERENCE LINK

https://www.panasonic.hk/english/products/living/ventilation-air-conditioning/split-air-conditioner.aspx#!/(compareUmbIds:!(),currentSubCatUmbId:’16613′,filterUmbIds:!(),paneMode:list,viewMode:thumblist)

Leave a Reply